PRODUCTS
-
Fire extinguishing system
-
Sprinkler hydrant
-
Fire extinguishing device
-
Internal storage pressure heptafluoropropane gas fire extinguishing equipment
-
External storage pressure heptafluoropropane gas fire extinguishing system
-
IG541 Mixed Gas Fire Extinguishing Equipment
-
Suspended heptafluoropropane gas fire extinguishing device
-
Cabinet type heptafluoropropane gas fire extinguishing device
-
Fire Extinguishing Equipment Accessories
-
-
Other
-
Product gallery
Suspended heptafluoropropane gas fire extinguishing device
Product description
The hanging heptafluoropropane fire extinguishing device is composed of a fire extinguishing agent storage container, a starting release component, a suspension bracket (seat), etc. that can be suspended or wall-mounted. The electromagnetic start type of the fire extinguishing device is activated by the linkage of the fire alarm, and the temperature-sensitive start type can automatically start the spray gas extinguishing agent. The product series is perfect, the appearance is beautiful, and it has the characteristics of flexible and convenient installation, accurate and reliable work, convenient operation and maintenance.
The structure of the hanging heptafluoropropane fire extinguishing device is composed of a retort, a container valve, a heptafluoropropane fire extinguishing agent, a safety discharge device, a nozzle, an electromagnetic drive device or a temperature-sensing starting component, a pressure display and a signal feedback device, and a kind of fully submerged fire extinguishing device installed in the form of suspension.
The main places and equipment commonly used for protection are: computer room, communication room, transformer, test center, transformer room, precision instrument room, physical and chemical laboratory, electrical aging room, oil depot and other flammable and flammable fuel oil and storage tanks, chemical and flammable product warehouse, library and other places.
Electronically controlled |
Temperature-controlled |
Product parameters
Parameter name | Performance parameters |
Model | XQQW(10\20)/1.6 XQQC(10\20)/1.6 |
How the device is applied | Fully submerged in applications |
The working environment conditions of the fire extinguishing device | Temperature 0°C~ +50°C: relative humidity ≤97% |
Design pressure | Maximum working pressure 2.5MPa |
Fire extinguishing agent storage pressure (20°C) | 1.6Mpa |
Storage capacity of fire extinguishing agent | 10L、20L |
Maximum filling density of fire extinguishing agent (20°C) | 1000kg/m3 |
Extinguishing agent spray time(s) | (S)≤10 |
The temperature sensing element operating temperature | 68℃ |